TOA : FS-7000CP TOA

Control Panel for FS-7000 Series Voice Evacuation System
หมายเลขสินค้า : FS-7000CP

ราคา 15,650.00 บาท

ราคาปกติ : 18,410.00 บาท

ประหยัดไป 2,760.00 บาท

*ราคาไม่รวมภาษีมูลค่าเพิ่ม 7%



เลือกจำนวน :

เลือกสี : สีดำ

  • สีดำ


แชร์ไปยัง :

Control Panel for FS-7000 Series Voice Evacuation System

 

The FS-7000CP Control Panel is the basic operation section for the FS-7000 Series Voice Evacuation System. It is designed to be used in conjunction with the FS-7000JP Junction Panel and can control up to 10 speaker zones and a simultaneous all-zone call.

* 0 dB = 1 V

Power Source

24 V DC, M3 screw terminal, distance between barriers: 6.4 mm

Current Consumption

200 mA

Input

EV: 0 dB*, 600 Ω, unbalanced, removable terminal block (2 pins)
Timer: 0 dB*, 600 Ω, unbalanced, removable terminal block (4 pins)
Paging: -60/-20 dB*, 600 Ω, balanced, removable terminal block (5 pins)
RF (Remote microphone): 0 dB*, 600 Ω, balanced,
removable terminal block (3 pins)
Preinstalled microphone (accessory): -55 dB*, 600 Ω, unbalanced,
circular connector (4 pins)
AUX: -20 dB*, 600 Ω, unbalanced, removable terminal block (2 pins)
BGM 1: -60/0 dB*, 600 Ω, balanced, removable terminal block (3 pins)
BGM 2 - 4: -20 dB*, 10 kΩ, unbalanced, RCA jack

Output

Priority output: 0 dB*, 600 Ω, balanced, removable terminal block (3 pins)
(Outputs signals other than BGM 1 - 4 input signals when output
is set to 2-channel broadcast mode.)
BGM output: 0 dB*, 600 Ω, balanced, removable terminal block (3 pins)
(Outputs BGM 1 - 4 signals.)

Frequency Response

50 - 15,000 Hz, within ±3 dB (1 kHz)

Tone Control

±10 dB at 100 Hz and 10 kHz

S/N Ratio

Over 60 dB

Distortion

Under 1%

Priority Function

Priority output: Preinstalled microphone > EV (emergency broadcast mode)
Timer > Paging > Remote microphone >
Preinstalled microphone, AUX > BGM 1
BGM 2 - 4 (general-purpose broadcast mode)
BGM output: BGM 1 BGM 2 - 4 (by muting function setting)

Electronic Tone

Ascending 4-tone chime

External Control Input

Timer: No-voltage make contact input, open voltage: 26 V DC,
short-circuit current: Under 2 mA, removable terminal block (4 pins)
Paging: No-voltage make contact input, open voltage: 26 V DC,
short-circuit current: Under 2 mA, removable terminal block (5 pins)
Automatic fire alarm system (10 zones):
No-voltage make contact input, open voltage: 26 V DC,
short-circuit current: Under 5 mA, removable terminal block (12 pins)

Output Control

10 individual zones + all-zone call or 10 group zones + all-zone call (when
optional FS-7000GM is connected)
(individual zones expandable to up to 200 zones using FS-7010CP)

Operating Section

Zone selection key, All-zone call button (general-purpose/general urgency all-
zone call selectable), Broadcast reset button and Chime button

Display Section

Power indicator, All-zone call indicator, Zone indicators, Busy indicator (timer,
paging, remote microphone and main system), Speaker line short-circuit indicator

Operating Temperature

0℃ to +40℃

Operating Humidity

Under 90% RH (no condensation)

Finish

Panel: Aluminum, black, alumite

Dimensions

482 (W) × 132.6 (H) × 376.9 (D) mm

Weight

5.2 kg

Accessory

Microphone …1, Removable terminal plug (2 pins) …2,
Removable terminal plug (3 pins) …4, Removable terminal plug (4 pins) …1,
Removable terminal plug (5 pins) …1, Removable terminal plug (12 pins) …1